ThermoSafe Services provides specialist thermostatic mixing valve (TMV) servicing, maintenance and performance testing for organisations throughout the UK.

We work with hospitals, schools, care homes, commercial properties and facilities management companies to maintain reliable hot water temperature control and reduce scalding risks.

Our services include planned TMV maintenance, routine servicing, TMV2 testing and TMV3 testing across individual properties and multi-site estates.

Hospital TMV Servicing and TMV3 Testing in Manchester

Project: Planned thermostatic mixing valve servicing and performance testing across a large hospital estate

Customer: Michael Thornton

Company: Northbridge Healthcare Facilities

Location: Manchester, Greater Manchester

Number of TMVs: 428

Project Duration: 10 working days

Services: Hospital TMV servicing, TMV3 testing, preventative maintenance and performance reporting

The Customer's Requirements

Northbridge Healthcare Facilities required a comprehensive TMV servicing programme across a hospital estate incorporating patient wards, outpatient departments, treatment rooms, accessible bathrooms and staff facilities.

The facilities management team needed to establish the condition and performance of existing thermostatic mixing valves, particularly those serving vulnerable patients.

Several departments had reported inconsistent mixed water temperatures, prompting the customer to arrange a detailed inspection and testing programme.

The customer also required updated servicing records identifying individual valve locations, test results, maintenance requirements and outstanding remedial work.

All servicing needed to take place within an operational healthcare environment without unnecessarily disrupting patient care.

Initial TMV Inspection and Asset Identification

ThermoSafe Services reviewed the existing asset register and identified thermostatic mixing valves across the hospital estate.

The initial assessment included:

  • Confirming individual TMV locations

  • Identifying valve manufacturers and models where possible

  • Establishing TMV3 approval status

  • Recording associated water outlets

  • Reviewing previous maintenance records

  • Identifying valves with restricted maintenance access

  • Assessing reported temperature control issues

  • Checking visible valve condition

Each accessible valve was recorded against its individual location, enabling the facilities management team to maintain a centralised record of servicing activity.

TMV3 Performance Testing

ThermoSafe Services carried out performance testing in accordance with the applicable valve specifications, manufacturer instructions and healthcare requirements.

The testing process included:

  • Hot water supply temperature measurements

  • Cold water supply temperature measurements

  • Stabilised mixed water outlet temperature checks

  • Temperature stability measurements

  • Cold water supply failure testing where applicable

  • Thermostatic shut-off performance checks

  • Temperature recovery assessments

  • Inspection for visible leaks and deterioration

Temperature readings were compared against the requirements of each outlet type and its designated application.

Healthcare outlets require careful temperature control because patients with reduced mobility, impaired sensation or other vulnerabilities may face an increased scalding risk.

Thermostatic Mixing Valve Servicing

The servicing programme identified several valves affected by limescale accumulation, internal debris and restricted movement of thermostatic components.

Maintenance work included:

  • Cleaning accessible internal components

  • Removing accumulated scale and debris

  • Cleaning inlet strainers

  • Inspecting seals and O-rings

  • Checking non-return valve operation

  • Inspecting thermostatic components

  • Reassembling valves following servicing

  • Adjusting mixed water temperatures where appropriate

  • Repeating performance tests following maintenance

Valves that could not be restored to the required performance standard were recorded for further investigation or replacement.

Working Within an Operational Hospital

ThermoSafe Services coordinated servicing activities with the hospital's estates management team and individual department representatives.

Work was scheduled around patient care requirements, clinical activities and departmental access restrictions.

Individual outlets were temporarily isolated during servicing and returned to use following satisfactory performance checks and the applicable site procedures.

The phased maintenance programme allowed the hospital to continue operating while servicing was completed across multiple departments.

Servicing Results

The initial inspection and testing programme identified:

  • 428 thermostatic mixing valves inspected

  • 356 valves meeting the required initial performance criteria

  • 49 valves requiring cleaning, adjustment or further servicing

  • 17 valves requiring replacement due to continued performance issues

  • 6 valves requiring further investigation

The 49 serviceable valves were restored to satisfactory performance following maintenance and repeat testing.

The remaining 23 valves were documented for further action, with recommendations provided to the estates management team.

The Outcome

The hospital received a detailed TMV servicing report containing individual asset references, temperature readings, performance test results and maintenance recommendations.

The programme identified deteriorating components and temperature control issues that could otherwise have remained undetected.

Updated servicing records enabled the estates management team to prioritise outstanding remedial work and establish an appropriate ongoing maintenance programme.

Project Takeaway: Regular hospital TMV servicing and TMV3 testing help identify valve deterioration and temperature control failures because healthcare environments contain users who may be particularly vulnerable to scalding.

Multi-Site School TMV Servicing Programme in Birmingham

Project: Planned TMV inspection, servicing and performance testing across a multi-academy trust

Customer: Rebecca Mills

Company: Westbrook Education Trust

Location: Birmingham, West Midlands

Number of Properties: 8 schools

Number of TMVs: 312

Project Duration: 8 working days

Services: TMV servicing for schools, TMV maintenance, temperature testing and asset register updates

The Customer's Requirements

Westbrook Education Trust required a coordinated thermostatic mixing valve servicing programme across eight primary and secondary schools.

The trust was responsible for maintaining controlled hot water temperatures across pupil washrooms, nursery facilities, accessible toilets, changing rooms and shower facilities.

Previous maintenance arrangements varied between individual schools, resulting in inconsistent servicing records and asset identification.

The customer wanted a single specialist contractor to inspect and service thermostatic mixing valves across the entire educational estate.

The servicing programme needed to take place during the school holidays to minimise disruption to pupils and teaching staff.

Initial Site Assessments

ThermoSafe Services reviewed existing maintenance records and carried out assessments across all eight schools.

The initial surveys established:

  • The number of installed thermostatic mixing valves

  • Individual valve locations

  • Valve accessibility

  • Associated washbasins and shower outlets

  • Existing temperature control arrangements

  • Visible signs of component deterioration

  • Previous servicing and testing history

  • Maintenance access requirements

Several previously unrecorded valves were identified beneath washbasins and within concealed service cupboards.

These assets were added to the trust's central maintenance register.

TMV Temperature and Performance Testing

ThermoSafe Services carried out temperature measurements and relevant performance tests across accessible thermostatic mixing valves.

Testing included supply water temperature measurements, stabilised mixed water temperature readings and thermostatic performance checks appropriate to each valve and application.

Particular attention was given to nursery washrooms, accessible facilities and outlets used by younger pupils.

Children may be more vulnerable to hot water injuries, making reliable temperature control particularly important within educational environments.

Thermostatic Mixing Valve Maintenance

Several valves presented inconsistent outlet temperatures due to internal scale deposits, debris and restricted component movement.

ThermoSafe Services completed appropriate maintenance work, including:

  • Cleaning inlet strainers

  • Removing internal scale deposits

  • Inspecting thermostatic components

  • Checking seals and non-return valves

  • Inspecting connections for leakage

  • Adjusting temperature settings where appropriate

  • Reassembling serviced valves

  • Repeating temperature and performance tests

Where maintenance could not restore satisfactory operation, individual valves were identified for replacement or further investigation.

Multi-Site Maintenance Coordination

The servicing programme was organised around the trust's school holiday maintenance schedule.

ThermoSafe Services coordinated access with individual site managers and central facilities management personnel.

Grouping multiple schools within a single maintenance programme reduced the administrative requirements associated with arranging separate contractor visits.

A consistent reporting format was used across all eight properties, allowing the trust to compare maintenance requirements between schools.

Servicing Results

The completed programme included:

  • 8 educational properties surveyed

  • 312 thermostatic mixing valves inspected

  • 267 valves meeting the required initial performance criteria

  • 34 valves restored to satisfactory performance following servicing

  • 11 valves identified for replacement or further investigation

  • 23 previously unrecorded valve locations added to the asset register

The customer received individual servicing records for each school alongside a consolidated estate-wide maintenance report.

The Outcome

ThermoSafe Services completed the eight-school servicing programme within the scheduled holiday maintenance period.

The trust gained an updated record of installed thermostatic mixing valves, associated outlets and individual maintenance requirements.

Identifying valves with deteriorating performance allowed the facilities management team to prioritise remedial work before pupils returned.

The centralised reporting system simplified future maintenance planning across the educational estate.

Project Takeaway: Multi-site TMV servicing programmes help educational organisations maintain consistent maintenance records because inspections, performance testing and remedial recommendations follow a standardised process across each property.

Care Home TMV Maintenance and TMV3 Testing in Leeds

Project: Thermostatic mixing valve maintenance and performance testing across a residential care facility

Customer: Jonathan Fisher

Company: Willowmere Residential Care

Location: Leeds, West Yorkshire

Number of Bedrooms: 96

Number of TMVs: 184

Project Duration: 5 working days

Services: TMV maintenance, TMV3 testing, temperature control assessments and preventative servicing

The Customer's Requirements

Willowmere Residential Care required a comprehensive TMV servicing programme across a residential and nursing care facility.

The property incorporated 96 resident bedrooms with en-suite facilities, communal bathrooms, assisted bathing facilities, accessible washrooms and staff accommodation.

The care home's maintenance team had identified fluctuating water temperatures at several outlets.

The customer required specialist testing to establish whether the temperature fluctuations originated from individual thermostatic mixing valves or wider water supply conditions.

As many residents required assistance with bathing and personal care, maintaining reliable outlet temperatures was particularly important.

The servicing programme needed to accommodate resident care routines and minimise disruption to occupied bedrooms.

Initial Temperature Control Assessment

ThermoSafe Services carried out an assessment of installed thermostatic mixing valves and their associated water outlets.

The assessment included:

  • Reviewing previous temperature monitoring records

  • Identifying reported temperature fluctuations

  • Confirming valve locations and intended applications

  • Reviewing valve manufacturer specifications

  • Checking hot and cold supply temperatures

  • Measuring stabilised mixed water temperatures

  • Assessing valve condition and accessibility

  • Identifying potential supply-related performance issues

Individual outlet requirements were reviewed according to the intended application rather than applying a single temperature setting throughout the property.

TMV3 Testing and Performance Checks

ThermoSafe Services carried out applicable TMV3 performance tests across outlets serving vulnerable residents.

The checks assessed temperature stability, thermostatic response and shut-off performance under the relevant test conditions.

Particular attention was given to assisted bathing facilities, communal showers and accessible bathrooms.

Thermostatic mixing valves in care environments perform an important protective function because residents may have reduced mobility or limited ability to respond to excessively hot water.

Valve Cleaning and Preventative Maintenance

The inspection identified recurring scale accumulation and debris within several thermostatic mixing valves.

Appropriate valves were isolated and dismantled in accordance with manufacturer instructions.

Maintenance activities included:

  • Cleaning internal valve components

  • Removing accumulated limescale

  • Cleaning and inspecting inlet strainers

  • Checking thermostatic element operation

  • Inspecting seals and connections

  • Checking non-return valve performance

  • Reassembling serviced components

  • Adjusting outlet temperatures where appropriate

  • Repeating applicable performance tests

Valves with persistent temperature instability or unsatisfactory shut-off performance were identified for replacement or further investigation.

Maintaining Resident Access and Safety

ThermoSafe Services coordinated individual servicing visits with care staff and the property's maintenance team.

Bedroom access was arranged around resident routines, personal care appointments and assisted bathing schedules.

Outlets undergoing servicing were temporarily removed from use until the required checks had been completed.

Any outstanding safety concerns were communicated to the care home's responsible personnel so that appropriate interim measures could be implemented.

Servicing Results

The maintenance programme included:

  • 184 thermostatic mixing valves inspected

  • 151 valves meeting the required initial performance criteria

  • 26 valves restored to satisfactory performance following servicing

  • 7 valves identified for replacement or further investigation

The customer received detailed temperature readings, individual performance test results and recommendations for outstanding maintenance work.

The Outcome

The five-day servicing programme identified thermostatic mixing valves affected by deteriorating internal components and scale accumulation.

Maintenance restored satisfactory performance to 26 valves, while seven valves were flagged for further action.

The care home received updated servicing records to support its ongoing water safety management arrangements.

ThermoSafe Services also provided recommendations for future inspection and maintenance intervals based on valve condition, manufacturer guidance and the risks associated with individual outlets.

Project Takeaway: Thermostatic mixing valve maintenance helps care providers manage scalding risks because regular performance testing identifies temperature instability and deterioration before further problems develop.

Commercial Property TMV2 Testing and Maintenance in London

Project: Thermostatic mixing valve servicing and TMV2 performance testing across a commercial office complex

Customer: Daniel Reeves

Company: Central Property Management Services

Location: London

Number of Buildings: 4

Number of TMVs: 236

Project Duration: 6 working days

Services: Commercial TMV servicing, TMV2 testing, preventative maintenance and asset reporting

The Customer's Requirements

Central Property Management Services required a coordinated TMV servicing programme across four commercial office buildings.

The properties incorporated communal washrooms, accessible toilets, staff kitchen facilities, shower rooms and changing facilities.

The customer wanted to assess existing valve performance, update maintenance records and identify equipment requiring servicing or replacement.

Previous servicing had been arranged separately across individual buildings, resulting in inconsistent documentation.

The facilities management company required a standardised maintenance and reporting process across the commercial estate.

Asset Identification and Condition Assessment

ThermoSafe Services completed an initial survey to establish the location, condition and intended application of installed thermostatic mixing valves.

Existing asset records were compared against equipment identified on site.

Individual valves were assessed for accessibility, visible deterioration, leakage, previous servicing history and appropriate approval classification.

The updated asset register provided a clear record of thermostatic mixing valves across all four buildings.

TMV2 Testing

ThermoSafe Services carried out TMV2 performance testing on applicable valves installed in domestic-type commercial applications.

Testing assessed:

  • Hot and cold water supply temperatures

  • Stabilised mixed water temperatures

  • Temperature control consistency

  • Applicable cold water supply failure performance

  • Valve recovery following supply restoration

  • Signs of leakage and deterioration

Valves serving higher-risk applications were assessed separately against their intended use and applicable requirements.

Planned TMV Servicing

Maintenance was completed on valves displaying inconsistent temperatures, restricted flow or signs of internal contamination.

The servicing work included cleaning strainers, removing scale and debris, inspecting seals, checking thermostatic components and repeating performance tests.

Adjustments were made where appropriate and permitted by the valve manufacturer's instructions.

Persistent faults were recorded against individual asset references to support subsequent remedial work.

Minimising Disruption to Commercial Occupants

ThermoSafe Services coordinated the maintenance programme with building managers and commercial tenants.

Servicing was completed in phases across individual floors and washroom facilities.

Temporary outlet isolation was managed around building occupancy and operational requirements.

This approach reduced the impact of maintenance activities on businesses occupying the properties.

Servicing Results

The completed commercial maintenance programme included:

  • 4 commercial office buildings surveyed

  • 236 thermostatic mixing valves inspected

  • 199 valves meeting the required initial performance criteria

  • 29 valves restored to satisfactory performance following maintenance

  • 8 valves identified for replacement or further investigation

The facilities management company received individual property reports and a consolidated commercial estate maintenance schedule.

The Outcome

The servicing programme provided the customer with a consistent record of valve performance across all four commercial properties.

Preventative maintenance addressed existing scale accumulation, internal debris and temperature control issues.

The updated asset register allowed the facilities management team to identify future servicing requirements and allocate maintenance budgets more effectively.

Project Takeaway: Planned commercial TMV maintenance supports reliable temperature control and efficient property management because individual valve conditions and outstanding remedial requirements are documented consistently.

What Do Our TMV Servicing Case Studies Demonstrate?

Thermostatic mixing valves require regular inspection, servicing and performance testing because internal components can deteriorate through normal use, scale accumulation and contamination.

ThermoSafe Services provides specialist maintenance solutions tailored to individual valve types, outlet applications and property requirements.

TMV Servicing

TMV servicing involves inspecting, cleaning and testing thermostatic mixing valves to assess their condition and temperature control performance.

Regular servicing helps identify internal deterioration, blocked strainers, scale accumulation and other issues that may affect valve operation.

TMV Maintenance

Planned TMV maintenance helps maintain reliable thermostatic performance and reduce unexpected valve failures.

Maintenance requirements depend on valve condition, water quality, manufacturer instructions, outlet usage and the risks associated with the application.

TMV2 Testing

TMV2 testing assesses the performance of thermostatic mixing valves approved for domestic and similar applications.

Performance testing helps establish whether installed valves continue to operate within the requirements of their designated application.

TMV3 Testing

TMV3 testing assesses thermostatic mixing valves designed for healthcare and higher-risk environments.

Hospitals, nursing homes and other care facilities require effective temperature control because vulnerable users may face an increased risk of scalding.

TMV Servicing for Schools

School TMV servicing helps educational organisations maintain controlled hot water temperatures across pupil washrooms, nursery facilities, accessible toilets and changing rooms.

Planned maintenance can be coordinated around school holidays and restricted access periods to minimise disruption.

TMV Servicing for Hospitals

Hospital TMV servicing involves inspecting, maintaining and testing thermostatic mixing valves across clinical and non-clinical environments.

Detailed servicing records help healthcare estates teams identify individual valve performance issues and prioritise necessary maintenance.

What Information Is Included in a TMV Servicing Report?

Detailed TMV servicing reports help facilities management teams monitor equipment performance and maintain an accurate maintenance history.

Depending on the scope of work, our servicing records can include:

  • Individual TMV asset references

  • Property and building details

  • Valve locations

  • Associated water outlets

  • Valve manufacturer and model

  • TMV approval classification where identifiable

  • Hot water supply temperatures

  • Cold water supply temperatures

  • Mixed water outlet temperatures

  • Applicable performance test results

  • Valve condition assessments

  • Maintenance work completed

  • Post-servicing test results

  • Identified defects

  • Replacement recommendations

  • Outstanding remedial requirements

  • Future maintenance recommendations

Clear documentation supports ongoing water safety management because responsible personnel can identify equipment condition, previous servicing activities and outstanding actions.

What Types of Properties Do We Service?

ThermoSafe Services provides thermostatic mixing valve servicing, maintenance and testing for organisations throughout the UK.

Our services accommodate:

  • NHS hospitals

  • Private hospitals

  • Healthcare centres

  • GP surgeries

  • Dental practices

  • Nursing homes

  • Residential care homes

  • Assisted living facilities

  • Primary schools

  • Secondary schools

  • Nurseries

  • Colleges

  • Universities

  • Commercial office buildings

  • Hotels

  • Leisure centres

  • Public buildings

  • Local authority properties

  • Industrial premises

  • Multi-site commercial estates

We provide individual servicing visits and coordinated maintenance programmes for organisations responsible for multiple properties.

Why Choose ThermoSafe Services?

ThermoSafe Services specialises in thermostatic mixing valve inspection, maintenance and performance testing.

Our services include:

  • Nationwide TMV servicing

  • Specialist TMV2 and TMV3 testing

  • Hospital and healthcare TMV maintenance

  • School and educational facility servicing

  • Commercial property TMV maintenance

  • Individual valve condition assessments

  • Temperature and performance testing

  • Preventative valve servicing

  • Multi-site maintenance programmes

  • Asset register updates

  • Detailed servicing documentation

  • Identification of faulty valves

  • Remedial maintenance recommendations

  • Flexible servicing arrangements

Our specialist approach helps organisations identify thermostatic mixing valve faults and maintain reliable servicing records across individual buildings and larger property estates.

How Much Does TMV Servicing Cost?

TMV servicing costs depend on the number of installed valves, property size, valve accessibility, testing requirements and maintenance complexity.

Larger properties and multi-site estates may benefit from coordinated servicing programmes because multiple thermostatic mixing valves can be assessed during scheduled maintenance visits.

Factors affecting TMV servicing prices include:

  • Number of thermostatic mixing valves

  • Valve manufacturer and model

  • TMV2 or TMV3 testing requirements

  • Property type and location

  • Valve accessibility

  • Existing valve condition

  • Cleaning and maintenance requirements

  • Asset identification requirements

  • Reporting requirements

  • Site access restrictions

  • Required servicing frequency

ThermoSafe Services provides tailored servicing packages based on individual property requirements, installed equipment and maintenance objectives.

How Often Should Thermostatic Mixing Valves Be Serviced?

Thermostatic mixing valve servicing frequency depends on manufacturer instructions, valve approval requirements, previous test results, water conditions and the risks associated with individual outlets.

Healthcare environments and facilities accommodating vulnerable users may require more frequent performance checks because the consequences of temperature control failures can be more severe.

An appropriate maintenance programme should reflect the property's water safety risk assessment and applicable technical guidance.

ThermoSafe Services can assess existing thermostatic mixing valves and recommend suitable inspection, testing and maintenance arrangements.

Looking for a Specialist TMV Servicing Company?

Whether you require hospital TMV servicing, school TMV maintenance, TMV2 testing or TMV3 performance testing, ThermoSafe Services provides specialist solutions tailored to your property requirements.

We work with healthcare organisations, educational establishments, care providers, commercial property owners and facilities management companies throughout the UK.

Our servicing programmes help identify valve faults, maintain reliable temperature control and support ongoing water safety management.

Get in Touch

Contact ThermoSafe Services today to discuss your thermostatic mixing valve servicing, maintenance and testing requirements.

Our team can provide a tailored maintenance programme based on your property type, number of installed valves, applicable testing requirements and ongoing maintenance objectives.

Get in Touch

We aim to get back to you in 1 working day.


Skip to

Privacy Information

Social Links

Contact

ThermoSafe Services
Trading style of Absolute Water Compliance Limited
Marland House
13 Huddersfield Road
Barnsley
S70 2LW

ThermoSafe Services is a trading style of Absolute Water Compliance Limited, registered in England & Wales (company no: 14264466)